Industrial chemicals · Taylor, TX
Certificate of Analysis

Sample Certificate of Analysis

Inhibited Ethylene Glycol 35/65 with OAT-908 — Data Center Coolant

34.98%

Category
Alcohols & Glycols (B)
Revision
1.9

Sample COA. Contact Alliance Chemical with your lot number to request a lot-specific COA.

CAS number
107-21-1
Structure
2D chemical structure of Inhibited Ethylene Glycol 35/65 with OAT-908 — Data Center Coolant
Structure · PubChem
Grade
34.98%
Assay specification
35.0 - 36.0 % w/w
Answer summary

Sample specification reference for Inhibited Ethylene Glycol 35/65 with OAT-908 — Data Center Coolant. Source-record results are reference values, not measurements for your lot.

Last reviewed 2026-07-17 by Andre Taki, Chief Commercial Officer, DOT Hazmat–certified (49 CFR 172.704).

Specifications

ParameterSpecificationSource reference resultTest Method
Assay (ethylene glycol)35.0 - 36.0 % w/w35.07 % w/w—
Reserve alkalinity1.05 ml min.5.6—
Nitrite840 ppm min.919 ppm—
Freezing Point-0.2 °F (-17.9 °C) max-0.3 °F (-17.9 °C)ASTM D1177
Density (Pounds per Gallon, 68 °F)8.728.72ASTM D4052
Electrical conductivity @ 25 °C3200 µS/cm maximum2546ASTM D1125
Chloride (as Cl)25 ppm maximum0.41 ppmASTM D3634
Silicates, phosphates, nitrites, borates, aminesNone added — < 10 ppm each0.53 ppmICP-OES / ion chromatography
Foaming tendency (volume / break time)150 mL max / 5 s maxPasses testASTM D1881
Acidity as Acetic Acid0.0018% max0.00008 %—
Diethylene Glycol0.018% max0.0108 %—
Iron (Fe)0.041 ppm max0.0072 ppm—
Residue after evaporation0.0019% max0.00030 %—
Sulfate (SO4)2.4 ppm max0.20 ppmTurbidimetric, ACS procedure
Heavy metals (as Pb)0.36 ppm max0.035 ppmICP-OES / ACS heavy metals procedure

Specification limits and source-record results are reproduced from the current product reference used by the TDS. This sample is not an issued certificate and does not identify a tested lot. Contact Alliance Chemical with the product and lot number for lot-specific documentation.

Need the Certificate of Analysis for your lot? Just ask.

Tell us the lot number from the container label and we will send the certificate over at no charge.

ProductInhibited Ethylene Glycol 35/65 with OAT-908 — Data Center Coolant