Industrial chemicals · Taylor, TX
Certificate of Analysis

Sample Certificate of Analysis

Inhibited Ethylene Glycol 30/70 with OAT-908 — Data Center Coolant

29.98%

Category
Alcohols & Glycols (B)
CAS番号
107-21-1
化学式
C2H6O2
Revision
1.5

Sample COA. Contact Alliance Chemical with your lot number to request a lot-specific COA.

2D chemical structure of Inhibited Ethylene Glycol 30/70 with OAT-908 — Data Center Coolant
Structure · PubChem
Last reviewed 2026-07-17 by Andre Taki, DOT Hazmat Specialist.

COA · Answer summary

Sample specification reference for Inhibited Ethylene Glycol 30/70 with OAT-908 — Data Center Coolant. Source-record results are reference values, not measurements for your lot.

Assay specification
29.0 - 31.0 % w/w

Specifications

ParameterSpecificationSource reference resultTest Method
Assay (ethylene glycol)29.0 - 31.0 % w/w30.0 % w/w
ASTM D1384 corrosion weight losscopper 10 max; solder 30 max; brass 10 max; steel 10 max; cast iron 10 max; aluminum 30 max mg/specimenPasses testASTM D1384
Freeze point6.7 °F (-14.1 °C) max6.7 °F (-14.1 °C)ASTM D1177
Reserve alkalinity0.9 ml min.4.8
Nitrite720 ppm min.810 ppm
Electrical conductivity @ 25 °C3000 µS/cm maximum2400ASTM D1125
Silicates, phosphates, nitrites, borates, aminesNone added — < 10 ppm each0.5 ppmICP-OES / ion chromatography
Foaming tendency (volume / break time)150 mL max / 5 s maxPasses testASTM D1881
Sulfate (SO4)2.2 ppm max0.15 ppmTurbidimetric, ACS procedure
Heavy metals (as Pb)0.31 ppm max0.03 ppmICP-OES / ACS heavy metals procedure
Identity (IR)passes testPasses test
Acidity as Acetic Acid0.0015% max0.00009 %
Chloride (Cl)0.43 ppm max0.03 ppm
Diethylene Glycol0.015% max0.006 %
Iron (Fe)0.037 ppm max0.006 ppm
Residue after evaporation0.0016% max0.0003 %
Color10 max1.6
Specific gravity (20 °C)1.035 - 1.0451.040
Composition30 % ethylene glycol in deionized water with the OAT-908 inhibitor package, by weightConformsBy formulation; confirmed by specific gravity

Specification limits and source-record results are reproduced from the current product reference used by the TDS. This sample is not an issued certificate and does not identify a tested lot. Contact Alliance Chemical with the product and lot number for lot-specific documentation.