Industrial chemicals · Taylor, TX
Certificate of Analysis

Sample Certificate of Analysis

Inhibited Propylene Glycol 50/50 with OAT Inhibitor — Data Center Coolant

50%

Category
Alcohols & Glycols (B)
Revision
1.7

Sample COA. Contact Alliance Chemical with your lot number to request a lot-specific COA.

CAS番号
57-55-6
構造
2D chemical structure of Inhibited Propylene Glycol 50/50 with OAT Inhibitor — Data Center Coolant
構造・PubChem
グレード
50%
Answer summary

Sample specification reference for Inhibited Propylene Glycol 50/50 with OAT Inhibitor — Data Center Coolant. Source-record results are reference values, not measurements for your lot.

Last reviewed 2026-07-16 by Andre Taki, Chief Commercial Officer, DOT Hazmat–certified (49 CFR 172.704).

Specifications

ParameterSpecificationSource reference resultTest Method
Propylene glycol content49.5 - 50.5 % w/w50.0 % w/wFormulation (batch weights); verified by refractive index against an in-house propylene glycol calibration / relative density (ASTM D1122)
AppearanceClear, colorless to pale yellow liquid, free of sediment and suspended matter (not dyed)ConformsVisual
Corrosion inhibitor package1.8 - 2.2 % w/w (nitrite-containing hybrid organic-acid)2.0 % w/wFormulation (batch weights)
Nitrite (as NO2)1,200 ppm min. (calculated 1,300–2,700 ppm at the 2.0% dose)ConformsFormulation minimum (calculated from inhibitor dose)
Freeze point-27 °F (-32.8 °C) maxapprox. -28 °F (-33 °C)ASTM D1177
pH, as supplied7.0 - 9.0 (typical)ConformsASTM D1287

Specification limits and source-record results are reproduced from the current product reference used by the TDS. This sample is not an issued certificate and does not identify a tested lot. Contact Alliance Chemical with the product and lot number for lot-specific documentation.

ロットの分析証明書が必要ですか?お気軽にお問い合わせください。

容器のラベルに記載されたロット番号をお知らせいただければ、無料で証明書をお送りします。

製品Inhibited Propylene Glycol 50/50 with OAT Inhibitor — Data Center Coolant