Industrial chemicals · Taylor, TX
Technical Data Sheet

Technical Data Sheet

Inhibited Propylene Glycol 30/70 with OAT Inhibitor — Data Center Coolant

30%

Alliance Code
SHOPIFY-7859429277738
Reviewed
2026-07-16
Revision
1.7
CAS number
57-55-6
Structure
2D chemical structure of Inhibited Propylene Glycol 30/70 with OAT Inhibitor — Data Center Coolant
Structure · PubChem
Grade
30%
Last reviewed 2026-07-16 by Andre Taki, Chief Commercial Officer.

Identity & Composition

Product Name
Inhibited Propylene Glycol 30/70 with OAT Inhibitor — Data Center Coolant
Alliance Code
SHOPIFY-7859429277738
Grade
—
Concentration
30%
CAS Number
57-55-6PubChem
Formula
C3H8O2PubChem
Molecular Weight
76.09PubChem
Product Type
Mixture

Specifications

TestSpecificationTypicalMethodSource
Propylene glycol content29.5 - 30.5 % w/w30.0 % w/wFormulation (batch weights); verified by refractive index against an in-house propylene glycol calibration / relative density (ASTM D1122)Interpreted
Corrosion inhibitor package1.8 - 2.2 % w/w (nitrite-containing hybrid organic-acid)2.0 % w/wFormulation (batch weights)Interpreted
Nitrite (as NO2)720 ppm min. (calculated 1,300–2,700 ppm at the 2.0% dose)ConformsFormulation minimum (calculated from inhibitor dose)Interpreted
Freeze point10 °F (-12.2 °C) maxapprox. 9 °F (-13 °C)ASTM D1177Interpreted

Values are reproduced from the current product reference. Source labels do not by themselves establish a supplier guarantee or a test result for your lot. Confirm applicable acceptance limits and request lot-specific documentation.

Available GradesSame CAS, alternate grades and concentrations

GradeConcentrationTypical AssaySKUTDS
This grade —30%—currentcurrent
—50%—SHOPIFY-7859432226858View TDS →
—40%—SHOPIFY-7859432194090View TDS →
—35%—SHOPIFY-7990713942058View TDS →
—25%—SHOPIFY-7990713909290View TDS →
—20%—SHOPIFY-15395850027241View TDS →

Typical assay shown is the rolling-window mean from the sibling product's most recent lots. Grade selection drives downstream end-use — verify the sibling grade matches your specification before substitution.

Physical & Chemical Properties

PropertyValueSource
AppearanceClear, colorless to pale yellow liquid, free of sediment and suspended matter (not dyed)Interpreted
OdorMild, characteristicAdjudicated
pH7.0 - 9.0 (typical)Interpreted
Specific Gravity1.027-1.035 (20 °C), calculated from formulationAdjudicated
Densityapprox. 1.03 g/mL (8.6 lb/gal) at 20 °CAdjudicated
Boiling Pointapprox. 102 °C (216 °F) at 760 mmHgAdjudicated
Melting PointFreeze point approx. -13 °C (9 °F) at 30 wt% propylene glycolAdjudicated
Flash PointNot flammable (aqueous solution)Adjudicated
Solubility (water)Miscible with waterAdjudicated

Regulatory & Transport

DOT / 49 CFR

UN Number
Not regulatedAdjudicated
Hazard Class
Not regulatedAdjudicated
Packing Group
Not regulatedAdjudicated
Proper Shipping Name
Not regulatedAdjudicated

GHS / OSHA HCS 2024

Signal Word
Not regulatedAdjudicated
H-Codes (Hazard Statements)
—no canonical
P-Codes (Precautionary Statements)
—no canonical

Occupational Exposure Limits

OSHA PEL (29 CFR 1910.1000)
—no canonical
ACGIH TLV
—no canonical
NIOSH REL
—no canonical
NIOSH IDLH
—no canonical

Transport descriptions reflect 49 CFR 172.101 lookup at time of publication. Sourced data: NIOSH Pocket Guide for REL/IDLH, OSHA Z-Tables for PEL. Always verify against the latest regulatory text before shipment-critical decisions.

Supplier Qualification Packet

One zipped download containing the TDS, SDS, latest lot COA (when available), and a fresh Letter of Continuing Guaranty for Inhibited Propylene Glycol 30/70 with OAT Inhibitor — Data Center Coolant. Every file included is SHA-256 hashed and listed in a manifest your QA team can audit.

Download audit packet

Application Guidance

Inhibited Propylene Glycol 30/70 with OAT Inhibitor — Data Center Coolant is a glycol-based heat-transfer and freeze-protection fluid. Concentration sets the freeze and burst protection; the inhibitor package sets how long the system stays protected from corrosion.

  • Closed-loop heat transfer and process cooling
  • Data-centre and chilled-water freeze protection
  • HVAC hydronic loops and glycol makeup
  • Freeze and burst protection for idle or seasonal systems

Verify concentration against the required freeze and burst protection, and confirm elastomer and metallurgy compatibility for the service temperature. Only a USP or food-grade propylene glycol is suitable where incidental food or potable contact is possible; inhibited grades are for closed-loop heat-transfer service only.

Storage & Handling

Recommended Storage
Keep closed in a cool place away from oxidizers. Protect from freezing below the rated freeze point. Stainless steel, carbon steel, polyethylene or polypropylene containers.Adjudicated
Handling Precautions
Chemical-resistant gloves and splash goggles. Avoid contact with hot surfaces and hot process equipment. Inhibitor packages deplete in service — monitor rather than top up blindly.Class-level guidance — not product-specific; the SDS controls.
Incompatibilities
Strong oxidizing agents; strong acids; strong bases.Adjudicated
Shelf Life
Consult Technical Services for product-specific shelf life

For full hazard, PPE, and emergency response guidance, refer to the Safety Data Sheet (SDS) for this product. The SDS controls in all cases where guidance differs.

Packaging & Logistics

Shipping Description (US DOT)

Not regulated for transport.

A package holding 22,700 lb (10,310 kg), about 2,620 US gal, or more of this product contains a reportable quantity (RQ) and ships as:

UN3082, Environmentally hazardous substance, liquid, n.o.s. (Sodium nitrite), 9, III, RQ

Confirm against shipping documents and carrier requirements before tender.

NMFC Class
55

Revision History

Last reviewed 2026-07-16 by Andre Taki, Chief Commercial Officer, DOT Hazmat–certified (49 CFR 172.704).

VersionDateChangeTrigger
1.72026-10-13Canonical data updated: 4 fields changed via the provenance/adjudication pipeline.
  • storage_precautions· canonical change (coa.data_provenance / adjudication)
  • incompatible_materials· canonical change (coa.data_provenance / adjudication)
  • conditions_to_avoid· canonical change (coa.data_provenance / adjudication)
  • hazardous_decomposition_products· canonical change (coa.data_provenance / adjudication)
canonical_change
1.62026-09-24Canonical data updated: 1 field changed via the provenance/adjudication pipeline.
  • physicalProperties· canonical change (coa.data_provenance / adjudication)
canonical_change
1.52026-09-17Canonical data updated: 1 field changed via the provenance/adjudication pipeline.
  • physicalProperties· canonical change (coa.data_provenance / adjudication)
canonical_change
1.42026-09-09Canonical data updated: 1 field changed via the provenance/adjudication pipeline.
  • physicalProperties· canonical change (coa.data_provenance / adjudication)
canonical_change
1.32026-07-24Canonical data updated: 1 field changed via the provenance/adjudication pipeline.
  • physicalProperties· canonical change (coa.data_provenance / adjudication)
canonical_change
1.22026-07-22Canonical data updated: 1 field changed via the provenance/adjudication pipeline.
  • ghsClassification· canonical change (coa.data_provenance / adjudication)
canonical_change
1.12026-07-16Canonical data re-verified: 10 fields updated against independent vendor SDSs, CLP Annex VI, 49 CFR, and OSHA HazCom 2024 (GHS classification, hazard/precautionary codes, signal word, physical properties as applicable).
  • countryOfOrigin· canonical adjudication / reground (coa.data_provenance)
  • dotProperShippingName· canonical adjudication / reground (coa.data_provenance)
  • dotSubsidiaryHazardClass· canonical adjudication / reground (coa.data_provenance)
  • ghsClassification· canonical adjudication / reground (coa.data_provenance)
  • hazardClass· canonical adjudication / reground (coa.data_provenance)
  • hsCode· canonical adjudication / reground (coa.data_provenance)
  • packingGroup· canonical adjudication / reground (coa.data_provenance)
  • physicalProperties· canonical adjudication / reground (coa.data_provenance)
  • signalWord· canonical adjudication / reground (coa.data_provenance)
  • unNumber· canonical adjudication / reground (coa.data_provenance)
canonical_change
1.02026-05-20Initial URL-first TDS published from canonical chemistry registry.initial

This Technical Data Sheet is provided for technical reference. The Safety Data Sheet (SDS) controls in all cases where guidance differs. Values reflect Alliance Chemical canonical data at time of generation; subsequent revisions are recorded in the Revision History above.