Industrial chemicals · Taylor, TX
Certificate of Analysis

Sample Certificate of Analysis

Inhibited Propylene Glycol 30/70 with OAT Inhibitor — Data Center Coolant

30%

Category
Alcohols & Glycols (B)
Revision
1.7

Sample COA. Contact Alliance Chemical with your lot number to request a lot-specific COA.

CAS number
57-55-6
Structure
2D chemical structure of Inhibited Propylene Glycol 30/70 with OAT Inhibitor — Data Center Coolant
Structure · PubChem
Grade
30%
Answer summary

Sample specification reference for Inhibited Propylene Glycol 30/70 with OAT Inhibitor — Data Center Coolant. Source-record results are reference values, not measurements for your lot.

Last reviewed 2026-07-16 by Andre Taki, Chief Commercial Officer, DOT Hazmat–certified (49 CFR 172.704).

Specifications

ParameterSpecificationSource reference resultTest Method
Propylene glycol content29.5 - 30.5 % w/w30.0 % w/wFormulation (batch weights); verified by refractive index against an in-house propylene glycol calibration / relative density (ASTM D1122)
AppearanceClear, colorless to pale yellow liquid, free of sediment and suspended matter (not dyed)ConformsVisual
Corrosion inhibitor package1.8 - 2.2 % w/w (nitrite-containing hybrid organic-acid)2.0 % w/wFormulation (batch weights)
Nitrite (as NO2)720 ppm min. (calculated 1,300–2,700 ppm at the 2.0% dose)ConformsFormulation minimum (calculated from inhibitor dose)
Freeze point10 °F (-12.2 °C) maxapprox. 9 °F (-13 °C)ASTM D1177
pH, as supplied7.0 - 9.0 (typical)ConformsASTM D1287

Specification limits and source-record results are reproduced from the current product reference used by the TDS. This sample is not an issued certificate and does not identify a tested lot. Contact Alliance Chemical with the product and lot number for lot-specific documentation.

Need the Certificate of Analysis for your lot? Just ask.

Tell us the lot number from the container label and we will send the certificate over at no charge.

ProductInhibited Propylene Glycol 30/70 with OAT Inhibitor — Data Center Coolant